Packaged Brackish Water Systems

  

Home Services Technology Products Projects Markets

General       MSI offers packaged Brackish Water RO Systems using the latest in membrane technology and state-of-the-art control systems.  Capacities range from 100 - 600 m3/day (18 - 110 gpm), Permeate Recovery 50-75% and Operating Pressure 10 - 31 Barg (150 - 450 psig)

Note:
Rated capacities are based on 2,000 ppm NaCl Solution @ 25 oC (77 oF); Operating Pressure 10 - 17  Barg (150 - 250 psig) for Thin Film Composite (TFC) membranes and 27 - 31 Barg (400 - 450 psig) for Cellulose Acetate (CA) membranes; and 50-75% Permeate Recovery, depending on feed water chemistry and system size.

Description

Type

Packaged Brackish Water RO Systems (BWRO)

Usage

Brackish Water (Well or Surface Water) Treatment

Applications

Drinking water, Process, Industrial

Equipment

The Packaged system is skid mounted and self contained.  The Medium Pressure Pump (MPP), Micron Filter, Low and High Pressure Piping as well as the Instrumentation and Controls are all mounted on the skid.  Local Control Panel (LCP) and Motor Starter Panel (MSP) are also mounted on the same skid.

Cleaning System can be mounted on the BWRO frame or furnished as a separate skid.  

Up to Three Chemical Pretreatment and Post Treatment Systems are provided as standard feature, and can be mounted on the BWRO frame or provided separately.

Capacity

Model Permeate Flow Weight Dimensions
(LxWxH)
gpd m3/d lb kg ft meters
B-100 26,400 100 770 350 10x4x6 3x1.5x2
B-200 26,400 200 1,650 750 10x4x6 3x1.5x2
B-300 39,600 300 2,430 1,100 22x4x6 7x1.5x2
B-400 52,800 400 2,870 1,300 22x4x6 7x1.5x2
B-500 66,000 500 3,750 1,700 22x4x6 7x1.5x2
B-600 79,300 600 3,970 1,800 22x4x6 7x1.5x2

Features

Pretreatment

Micron Filter and up to Two of Chemical injection systems are provided as standard feature.   Clarifiers and/ or Media Filters are optional. 

Main Treatment

Membrane Separation Systems using high or standard rejection RO membrane elements, Softening NF membranes, UF membranes or MF elements

Post Treatment 

Up to One Chemical Treatment System is provided.  UV Sterilizer, Ozonation or Post Chlorination are optional

 Supporting Equipment   A dedicated Cleaning System is provided.  Depending on membrane system capacity, the cleaning system could be mounted on the RO support structure or on a separate skid

Instruments

Locally mounted primary elements, Monitoring and Control Instruments are mounted on the Local Control Panel (LCP)

Controls

PLC based microprocessor, located inside the LCP

Advantages

Design

1.  Reliable, high quality components
2.  Excellent corrosion resistance
3.  Compact, small equipment footprint
4.  Conservatively designed for consistent, trouble free operation

Operations

Reliable; slow start; safety interlocks; lower capital and operating cost

Performance

Product water TDS content of less than 500 mg/l per WHO standards.  Higher quality product can be obtained by further treatment in a Polishing Loop.

Components

Pretreatment

1.  Chemical Treatment:   Antiscalant and Acid injection systems.
2.  Micron Filtration:  5 micron Cartridge filters in FRP or 316SS Housing.

Main Treatment
(RO Unit)

RO Medium Pressure Pump (MPP) Multistage Centrifugal type.  Discharge pressure up to 600 psig.

1.  Membrane Elements:  Type depends on the application e.g. High or Standard Rejection; Low Pressure; High Flux CTA or TFC Membrane elements 4" or 8" x 40" (D x L)
2.  Pressure Vessel Assemblies: FRP rated for 150-600 psig, housing the membrane elements.
3.  Support structure Structure: FRP or CS epoxy painted or powder coated, supporting the pressure vessel assemblies

Piping

 1.  Train mounted High Pressure piping: Fabricated of Sch 40 or 10 316L Stainless Steel
 2.  Train mounted Low Pressure piping: Fabricated of Sch 10 316L SS or  Sch 80 PVC

Valves

1.  Control Valves: Modulating, with Pneumatic or Electrical Actuator
2.  Auto Isolation Valves: Pneumatic or Electrical operator w/ Auto On-Off control
3.  Manual Valves: SS or Plastic, as required

 Instruments  Provided for continuous monitoring and/ or control of Flow, Pressure,  Temperature, Level and Analytical parameters, such as pH, Conductivity, ORP, Turbidity, etc.
 Controls  Programmable Logic Controller (PLC), mounted inside the Local Control Panel (LCP)
 Electrical  Skid mounted Local Starter Panel (LSP), Junction Boxes and Miscellaneous hardware

Options

1.  Media Filters
2.  UV Sterilizers, Ozonators or Chlorinators
4.  Adjustable Frequency Drive (AFD) for the Medium Pressure Pump (MPP)
5.  Data Acquisition and Monitoring System (DAQM) 

 

 

 

                           Up ] Packaged Seawater Systems ] [ Packaged Brackish Water Systems ]
                       
                         

                              Please Send mail to CompanyWebmaster with questions or comments about this web site
                                Copyright © 1999 CompanyLongName